[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935859":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935859,605,1,"单选题","下列关于水泵接合器做法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","水泵接合器距室外消火栓30m",true,{"key":16,"text":17,"correct":18},"B","地下水泵接合器进水口和井盖地面的距离不小于0．4m，且不应小于井盖半径",false,{"key":20,"text":21,"correct":18},"C","安装高度距地面为0．9m",{"key":23,"text":24,"correct":18},"D","组装式水泵接合器按接口、本体、连接管、安全阀、止回阀、放空管、控制阀的顺序进行","A正确，水泵接合器距室外消火栓15～40m。B错，地下水泵接合器安装应使进水口和井盖地面的距离不大于0．4m，且不应小于井盖半径；C错，安装高度距地面宜为0．7m；D错，组装式水泵接合器的安装应按接口、本体、连接管、止回阀、安全阀、放空管、控制阀的顺序进行。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]