[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935851":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935851,605,1,"单选题","某综合楼的自动喷水灭火系统的设计工作压力为0．9MPa，消防工程施工单位对系统的钢管管道进行水压试验，则该系统的水压强度试验不应低于（ ）MPa。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1．35",false,{"key":16,"text":17,"correct":14},"B","1．5",{"key":19,"text":20,"correct":14},"C","1．3",{"key":22,"text":23,"correct":24},"D","1．4",true,"根据《自动喷水灭火系统施工及验收规范》GB 50261—20176．2．1，当系统设计工作压力等于或小于1．0MPa时，水压强度试验压力应为设计工作压力的1．5倍，并不应低于1．4MPa；当系统设计工作压力大于1．0MPa时，水压强度试验压力应为该工作压力加0．4MPa。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]