[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935849":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935849,605,2,"多选题","下列关于消防给水系统减压阀的安装要求的说法中，正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","减压阀安装应在供水管网试压、冲洗合格后进行",true,{"key":16,"text":17,"correct":14},"B","减压阀水流方向应与供水管网水流方向一致",{"key":19,"text":20,"correct":21},"C","减压阀后应有过滤器",false,{"key":23,"text":24,"correct":14},"D","减压阀前后应安装压力表",{"key":26,"text":27,"correct":21},"E","减压阀处应有压力试验用排水设施，排水管直径不应小于DN75","ABD","《消防给水及消火栓系统技术规范》（GB 50974-2014），12.3.26。选项C，过滤器应在减压阀前。选项E，排水管直径不应小于DN100。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]