[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935848":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935848,605,2,"多选题","消防给水系统和各类水灭火设施测试的时候需要有排水功能，下列关于测试排水要求的说法中，正确的有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","末端试水装置处的排水立管管径，应根据末端试水装置的泄流量确定，并不宜小于DN75",true,{"key":16,"text":17,"correct":14},"B","报警阀处的排水立管宜为DN100",{"key":19,"text":20,"correct":14},"C","减压阀处的压力试验排水管道直径应根据减压阀流量确定，但不应小于DN100",{"key":22,"text":23,"correct":24},"D","每台消防水泵出水管上应设置DN75的试水管，并应采取排水措施",false,{"key":26,"text":27,"correct":14},"E","试验排水可回收部分宜排入专用消防水池循环再利用","ABCE","《消防给水及消火栓系统技术规范》（GB 50974-2014），5.1.11,9.3。选项D，试水管应为DN65。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]