[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935838":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935838,605,1,"单选题","在消防给水管网的安装过程中，下列关于防晃支架设置的说法，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","管径大于DN50mm的管道拐弯、三通及四通位置处应设1个防晃支架",false,{"key":16,"text":17,"correct":14},"B","配水管宜在中点设一个防晃支架，当管径小于DN50mm时可不设",{"key":19,"text":20,"correct":14},"C","配水干管及配水管、配水支管的长度超过15m，每15m长度内应至少设1个防晃支架，当管径不大于DN40mm可不设",{"key":22,"text":23,"correct":24},"D","防晃支架的强度应满足管道、配件及管内水的重量再加20％的水平方向推力时不损坏或不产生永久变形",true,"消防给水管网的下列部位应设置固定支架或防晃支架：（1）配水管宜在中点设一个防晃支架，当管径小于DN50 mm时可不设。（2）配水干管及配水管、配水支管的长度超过15 m，每15 m长度内应至少设1个防晃支架，当管径不大于DN40 mm可不设。（3）管径大于DN50 mm的管道拐弯、三通及四通位置处应设1个防晃支架。（4）防晃支架的强度，应满足管道、配件及管内水的重量再加50％的水平方向推力时不损坏或不产生永久变形。当管道穿梁安装时，管道再用紧固件固定于混凝土结构上，可作为1个防晃支架处理。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]