[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935836":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935836,605,1,"单选题","对消防给水系统管网进行气压严密性试验，下列关于试验压力和保压时间的说法，正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","试验压力为3．0MPa，保压时间为3min",false,{"key":16,"text":17,"correct":14},"B","试验压力为0．05MPa，保压时间为30min",{"key":19,"text":20,"correct":14},"C","试验压力为1．0MPa，保压时间为24h",{"key":22,"text":23,"correct":24},"D","试验压力为0．28MPa，保压时间为24h",true,"根据《消防给水及消火栓系统技术规范》GB 50974—201412．4．7，气压严密性试验的介质宜采用空气或氮气，试验压力应为0．28MPa，且稳压24h，压力降不应大于0．01MPa。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]