[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935828":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935828,605,1,"单选题","下列有关减压阀调试的说法中，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","减压阀达到设计流量的150％时不应出现噪声明显增加",false,{"key":16,"text":17,"correct":18},"B","减压阀的出流量为设计流量的150％时，阀后动压应小于额定设计工作压力的65％",true,{"key":20,"text":21,"correct":14},"C","测试减压阀的阀后动静压差应符合设计要求",{"key":23,"text":24,"correct":14},"D","减压阀的阀前阀后动静压力应满足设计要求","根据《消防给水及消火栓系统技术规范》GB 50974—201413．1．7，减压阀调试应符合下列要求： 1）减压阀的阀前阀后动静压力应满足设计要求。 2）减压阀的出流量应满足设计要求，当出流量为设计流量的150％时，阀后动压不应小于额定设计工作压力的65％。 3）减压阀在小流量、设计流量和设计流量的150％时不应出现噪声明显增加。 4）测试减压阀的阀后动静压差应符合设计要求。 本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]