[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935821":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935821,605,1,"单选题","消防水池的施工安装，要注意消防水池的外壁与建筑本体结构墙面或其他池壁之间的净距。无管道的侧面，净距不宜小于 0.7 m；有管道的侧面，净距不宜小于（ ） m，且管道外壁与建筑本体墙面之间的通道宽度不宜小于（ ） m。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.9， 0.6",false,{"key":16,"text":17,"correct":18},"B","1.0， 0.6",true,{"key":20,"text":21,"correct":14},"C","0.9， 0.5",{"key":23,"text":24,"correct":14},"D","1.0， 0.5","在施工安装时，消防水池及消防水箱的外壁与建筑本体结构墙面或其他池壁之间的 净距，要满足施工、装配和检修的需要。无管道的侧面，净距不宜小于 0.7 m; 有管道的侧面， 净距不宜小于1.0 m ，且管道外壁与建筑本体墙面之间的通道宽度不宜小于 0.6 m; 设有人孔的 池顶，顶板面与上面建筑本体板底的净空不应小于 0.8 m。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]