[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935818":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935818,605,1,"单选题","根据现行国家标准《自动喷水灭火系统施工及验收规范》GB 50261—2017，下列关于自动喷水灭火系统试验前应具备的条件，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","试压用的压力表不应少于2只，精度不应低于1．5级，量程应为试验压力值的2．0倍～2．5倍",true,{"key":16,"text":17,"correct":18},"B","试压冲洗方案已经批准",false,{"key":20,"text":21,"correct":18},"C","埋地管道的位置及管道基础、支墩等经复查应符合设计要求",{"key":23,"text":24,"correct":18},"D","对不能参与试压的设备、仪表、阀门及附件应加以隔离或拆除","根据现行国家标准《自动喷水灭火系统施工及验收规范》GB 50261—2017，6．1．5—2，试压用的压力表不应少于2只；精度不应低于1．5级，量程应为试验压力值的1．5倍～2．0倍。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]