[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935816":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935816,605,1,"单选题","分区供水形式应根据系统压力、建筑特征，经技术经济和安全可靠性等综合因素确定，某消火栓系统当系统工作压力大于2．4MPa时，应采用（ ）形式。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","消防水泵并行",false,{"key":16,"text":17,"correct":14},"B","减压稳压消火栓",{"key":19,"text":20,"correct":14},"C","减压阀减压",{"key":22,"text":23,"correct":24},"D","消防水泵直接串联",true,"根据《消防给水及消火栓系统技术规范》GB 50974—20146．2．2，分区供水形式应根据系统压力、建筑特征，经技术经济和安全可靠性等综合因素确定，可采用消防水泵并行或串联、减压水箱和减压阀减压的形式，但当系统的工作压力大于2．40MPa时，应采用消防水泵串联或减压水箱分区供水形式。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]