[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935815":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935815,605,1,"单选题","关于消防给水管道的安装，以下说法错误的是（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","管径小于DN50时配水管中点可不设防晃支架",false,{"key":16,"text":17,"correct":18},"B","管道变径当采用补芯时，三通上可用二个，四通上不应超过三个",true,{"key":20,"text":21,"correct":14},"C","消防给水管穿过楼板时应加套管，套管应高出地面50mm",{"key":23,"text":24,"correct":14},"D","公称直径大于50mm的管道不宜使用活接头","根据《消防给水及消火栓系统技术规范》GB 50974—201412．3．20—6—1，配水管宜在中点设一个防晃支架，但当管径小于DN50时可不设，A选项正确；根据12．3．12—8，采用沟槽连接件连接管道变径和转弯时，宜采用沟槽式异径管件和弯头。当需要采用补芯时，三通上可用一个，四通上不应超过二个，公称直径大于50mm的管道不宜采用活接头，B选项错误，D选项正确；根据12．3．19—5，消防给水管穿过墙体或楼板时应加设套管，套管长度不应小于墙体厚度，或应高出楼面或地面50mm，C选项正确。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]