[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935807":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935807,605,1,"单选题","某消防检测机构对消防水泵进行验收时，验收结果如下，其中不符合规范要求的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","吸水管、出水管上的控制阀锁定在常开位置，且有明显标记",false,{"key":16,"text":17,"correct":14},"B","打开消防水泵出水管上试水阀，当采用主电源启动消防水泵时，消防水泵启动正常",{"key":19,"text":20,"correct":14},"C","消防水泵启动控制置于自动启动挡",{"key":22,"text":23,"correct":24},"D","消防水泵停泵时，水锤消除设施后的压力超过水泵出口设计压力的1．4倍",true,"根据《自动喷水灭火系统施工及验收规范》GB 50261—201713．2．6—6，消防水泵停泵时，水锤消除设施后的压力不应超过水泵出口设计工作压力的1．4倍。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]