[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935806":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935806,605,1,"单选题","对某建筑设置的消防水池进行检查，下列检查结果中可以判定不符合相关规定的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","消防水池进水管管径为DN125",false,{"key":16,"text":17,"correct":14},"B","消防水池的取水口与水泵房之间的距离为10m",{"key":19,"text":20,"correct":14},"C","消防水池设置有溢流水管和排水设施，并采用间接排水",{"key":22,"text":23,"correct":24},"D","供消防车取水的消防水池取水口高度为8．0m",true,"根据《消防给水及消火栓系统技术规范》GB 50974—20144．3．3，消防水池进水管应根据其有效容积和补水时间确定，补水时间不宜大于48h，但当消防水池有效总容积大于2000m3时，不应大于96h；消防水池进水管管径应经计算确定，且不应小于DN100，A选项正确；根据4．3．7—2，消防水池的取水口与建筑物（水泵房除外）的距离不宜小于15m，规范没有规定取水口与水泵房之间的距离，B选项正确；根据4．3．9—3，消防水池应设置溢流水管和排水设施，并应采用间接排水，C选项正确；根据4．3．7—1，储存室外消防用水的消防水池或供消防车取水的消防水池，消防水池应设置取水口（井），且吸水高度不应大于6．0m，D选项错误。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]