[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935804":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935804,605,2,"多选题","根据现行国家标准《自动喷水灭火系统施工及验收规范》GB 50261—2017，下列关于报警阀组的安装要求中，不正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","安装时应先安装报警阀，然后安装水源控制阀并进行报警阀辅助管道的连接",true,{"key":16,"text":17,"correct":18},"B","报警阀组的安装应在供水管网试压、冲洗合格后进行",false,{"key":20,"text":21,"correct":18},"C","距室内地面高度宜为1．2m",{"key":23,"text":24,"correct":18},"D","两侧与墙的距离不应小于0．5m",{"key":26,"text":27,"correct":14},"E","正面与墙的距离不应小于1．5m","AE","根据《自动喷水灭火系统施工及验收规范》GB 50261—20175．3．1，报警阀组的安装应在供水管网试压、冲洗合格后进行。安装时应先安装水源控制阀、报警阀，然后进行报警阀辅助管道的连接。水源控制阀、报警阀与配水干管的连接，应使水流方向一致。报警阀组安装的位置应符合设计要求；当设计无要求时，报警阀组应安装在便于操作的明显位置，距室内地面高度宜为1．2m；两侧与墙的距离不应小于0．5m；正面与墙的距离不应小于1．2m；报警阀组凸出部位之间的距离不应小于0．5m。安装报警阀组的室内地面应有排水设施，排水能力应满足报警阀调试、验收和利用试水阀门泄空系统管道的要求。本题答案为AE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]