[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935800":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935800,605,1,"单选题","某建筑消防给水系统使用2台型号一致的消防水泵组成泵组（一用一备），单台设计流量35L\u002Fs，设计工作压力为0.90MPa。该泵组设置的压力检测装置的最大量程至少应大于（ ）MPa。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1.80",false,{"key":16,"text":17,"correct":18},"B","1.98",true,{"key":20,"text":21,"correct":14},"C","2.25",{"key":23,"text":24,"correct":14},"D","2.70","《消防给水及消火栓系统技术规范》（GB 50974-2014），5.1.11-3，消防水泵压力检测装置的计量精度应为0.5级，最大量程的75％应大于最大一台消防水泵设计压力值的165％；0.90×165%÷75%=1.98。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]