[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935785":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935785,605,1,"单选题","对防烟排烟系统进行验收的过程中，竣工验收判定结论为合格的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","A=0，B=3，B+C=4",false,{"key":16,"text":17,"correct":14},"B","A=0，B=2，B+C=8",{"key":19,"text":20,"correct":21},"C","A=0，B=2，B+C=5",true,{"key":23,"text":24,"correct":14},"D","A=1，B=2，B+C=3","消防设施现场检查结束后，根据各类设施的施工及验收规范确定的工程施工质量缺陷类别，按照下列规则对各类消防设施的施工质量作出验收判定结论：消防给水及消火栓系统、自动喷水灭火系统、防烟排烟系统和火灾自动报警系统等工程施工质量缺陷划分为严重缺陷项（A）、重缺陷项（B）和轻缺陷项（C）。消防给水及消火栓系统、自动喷水灭火系统、防烟排烟系统的工程施工质量缺陷，当A=0，B≤2，且B+C≤6时，竣工验收判定为合格；否则，竣工验收判定为不合格。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]