[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935738":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935738,605,1,"单选题","对设备用房进行防火检查，应注意设备用房的内部装修材料燃烧性能等级，下列设备用房中，内部装修材料的燃烧性能等级与其他选项不同的（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","消防水泵房",false,{"key":16,"text":17,"correct":18},"B","消防控制室",true,{"key":20,"text":21,"correct":14},"C","变压器室",{"key":23,"text":24,"correct":14},"D","机械加压送风机房","根据《建筑内部装修设计防火规范》GB 50222—20174．0．9，消防水泵房、机械加压送风排烟机房、固定灭火系统钢瓶间、配电室、变压器室、发电机房、储油间、通风和空调机房等，其内部所有装修均应采用A级装修材料；根据4．0．10，消防控制室等重要房间，其顶棚和墙面应采用A级装修材料，地面及其他装修应采用不低于B---1级的装修材料。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]