[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935730":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935730,605,2,"多选题","下列关于通风、空调设备的防火防爆说法正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","两条输送气体的管道上下布置时，表面温度70℃的管道设在表面温度120℃的管道下方",true,{"key":16,"text":17,"correct":14},"B","燃油锅炉房采用机械通风时的正常通风量应按换气次数不少于3次／h",{"key":19,"text":20,"correct":21},"C","燃气锅炉房采用机械通风时事故排风量应按换气次数不少于6次／h确定",false,{"key":23,"text":24,"correct":14},"D","燃气锅炉房应选用防爆型的事故排风机",{"key":26,"text":27,"correct":14},"E","排风系统应设置导除静电的接地装置","ABDE","根据《建筑设计防火规范》GB 50016—2014（2018年版）9．3．10，排除和输送温度超过80℃的空气或其他气体以及易燃碎屑的管道，与可燃或难燃物体之间的间隙不应小于150mm，或采用厚度不小于50mm的不燃材料隔热；当管道上下布置时．表面温度较高者应布置在上面，A选项正确；根据9．3．16，燃油或燃气锅炉房应设置自然通风或机械通风设施。燃气锅炉房应选用防爆型的事故排风机。当采取机械通风时，机械通风设施应设置导除静电的接地装置，通风量应符合下列规定：1）燃油锅炉房的正常通风量应按换气次数不少于3次／h确定，事故排风量应按换气次数不少于6次／h确定；2）燃气锅炉房的正常通风量应按换气次数不少于6次／h确定，事故排风量应按换气次数不少于12次／h确定，BD选项正确，C选项错误；根据9．3．9—1，排除有燃烧或爆炸危险气体、蒸气和粉尘的排风系统应设置导除静电的接地装置，E选项正确。本题答案ABDE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]