[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935725":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935725,605,1,"单选题","下列关于有爆炸危险的厂房的总体布局说法中，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","有爆炸危险的甲、乙类厂房的总控制室应独立设置",false,{"key":16,"text":17,"correct":14},"B","分控制室宜独立设置，当贴邻厂房外墙设置时，应采用耐火极限不低于3．00h的防火隔墙与其他部位分隔",{"key":19,"text":20,"correct":21},"C","净化有爆炸危险粉尘的干式除尘器和过滤器宜布置在厂房内靠外墙一侧",true,{"key":23,"text":24,"correct":14},"D","有爆炸危险的甲、乙类厂房宜独立设置","根据《建筑设计防火规范》GB 50016—2014（2018年版）3．6．8，有爆炸危险的甲、乙类厂房的总控制室应独立设置，A选项正确；根据3．6．9，有爆炸危险的甲，乙类厂房的分控制室宜独立设置，当贴邻外墙设置时，应采用耐火极限不低于3．00h的防火隔墙与其他部位分隔，B选项正确；根据9．3．7，净化有爆炸危险粉尘的干式除尘器和过滤器宜布置在厂房外的独立建筑内，建筑外墙与所属厂房的防火间距不应小于10m，C选项错误；根据3．6．1，有爆炸危险的甲、乙类厂房宜独立设置，D选项正确。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]