[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935723":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935723,605,2,"多选题","下列关于建筑防爆采取的防爆措施检查要求的叙述中，正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","有爆炸危险的甲、乙类厂房宜独立设置",false,{"key":16,"text":17,"correct":14},"B","有爆炸危险的设备应避开厂房的梁、柱等主要承重构件布置",{"key":19,"text":20,"correct":21},"C","散发可燃粉尘、纤维的厂房内地面应平整、光滑，并易于清扫",true,{"key":23,"text":24,"correct":21},"D","甲、乙、丙类液体仓库设置防止液体流散的设施",{"key":26,"text":27,"correct":21},"E","遇湿会发生燃烧爆炸的物品仓库应采取防止水浸渍的措施","CDE","主要检查有爆炸危险的厂房、仓库是否采取有效的防爆措施。检查要求为： （1）散发较空气重的可燃气体、可燃蒸气的甲类厂房和有粉尘、纤维爆炸危险的乙类厂房，其地面采用不发火花的地面。 （2）散发可燃粉尘、纤维的厂房内地面平整、光滑，并易于清扫。 （3）使用和生产甲、乙、丙类液体厂房，其管、沟不得与相邻厂房的管、沟相通，下水道设置隔油设施，避免流淌或滴漏至地下管沟的液体遇火源后引起燃烧爆炸事故并殃及相邻厂房。 （4）甲、乙、丙类液体仓库设置防止液体流散的设施。 （5）遇湿会发生燃烧爆炸的物品仓库采取防止水浸渍的措施。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]