[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935721":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935721,605,2,"多选题","在对容易发生火灾或爆炸的厂房进行防火检查时，应注意检查其供暖系统的设置情况，下列做法中，不符合现行国家消防技术标准要求的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","在散发可燃纤维的厂房内，散热器表面的平均温度为83.5℃",true,{"key":16,"text":17,"correct":18},"B","在散发可燃粉尘的厂房内，输煤廊的散热器表面平均温度为130℃",false,{"key":20,"text":21,"correct":18},"C","甲类厂房内的供暖管道和设备的绝热材料采用不燃材料",{"key":23,"text":24,"correct":14},"D","外壁温度为120℃的供暖管道与可燃构件之间的最近距离为90mm",{"key":26,"text":27,"correct":14},"E","外壁温度为90℃的供暖管道与可燃构件之间的最近距离为35mm","ADE","选项A，不得超过82.5℃。选项D，距离不应小于100mm。选项E，距离不应小于50mm。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]