[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935708":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935708,605,1,"单选题","对地下采用机械通风系统的燃油锅炉房进行防火检查时，应检查风机排风量换气次数是否符合规范要求，其中下列关于燃油锅炉房风机通风量的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","正常通风量应按换气次数不少于3次／h确定",true,{"key":16,"text":17,"correct":18},"B","事故排风量应按换气次数不少于5次／h确定",false,{"key":20,"text":21,"correct":18},"C","事故排风量应按换气次数不少于9次／h确定",{"key":23,"text":24,"correct":18},"D","正常通风量应按换气次数不少于6次／h确定","根据《建筑设计防火规范》GB 50016—2014（2018年版）9．3．16—1，燃油应设置自然通风或机械通风设施，燃油锅炉房的正常通风量应按换气次数不少于3次／h确定，事故排风量应按换气次数不少于6次／h确定。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]