[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935707":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935707,605,1,"单选题","根据现行国家消防技术标准，下列关于除尘器、过滤器等设施设置的说法，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","净化有爆炸危险粉尘的干式除尘器应布置在系统的负压段上",false,{"key":16,"text":17,"correct":14},"B","净化或输送有爆炸危险粉尘和碎屑的除尘器应设置泄压装置",{"key":19,"text":20,"correct":21},"C","净化有爆炸危险粉尘的干式除尘器和过滤器宜布置在厂房内的独立房间",true,{"key":23,"text":24,"correct":14},"D","对于遇水可能形成爆炸的粉尘，严禁采用湿式除尘器","根据《建筑设计防火规范》GB 50016—2014（2018年版）9．3．8，净化或输送有爆炸危险粉尘和碎屑的除尘器、过滤器或管道，均应设置泄压装置，净化有爆炸危险粉尘的干式除尘器和过滤器应布置在系统的负压段上，AB选项正确；根据9．3．7，净化有爆炸危险粉尘的干式除尘器和过滤器宜布置在厂房外的独立建筑内，建筑外墙与所属厂房的防火间距不应小于10m，C选项错误；根据9．3．5，含有燃烧和爆炸危险粉尘的空气，在进入排风机前应采用不产生火花的除尘器进行处理。对于遇水可能形成爆炸的粉尘，严禁采用湿式除尘器，D选项错误。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]