[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935642":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935642,605,2,"多选题","下列关于疏散走道最小净宽度的说法，符合现行国家技术标准的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","高层病房楼双面布房时的疏散走道最小净宽度不应小于1．40m",false,{"key":16,"text":17,"correct":18},"B","高层办公建筑单面布房时的疏散走道的最小净宽度不应小于1．30m",true,{"key":20,"text":21,"correct":18},"C","厂房内疏散走道的最小净宽度不宜小于1．40m",{"key":23,"text":24,"correct":18},"D","人防工程内商场单面布房疏散走道的净宽度不应小于1．50m",{"key":26,"text":27,"correct":14},"E","剧场观众厅内疏散走道的净宽度不应小于1．10m","BCD","根据《建筑设计防火规范》GB 50016—2014（2018年版）表5．5．18，高层病房楼双面布房时，疏散走道的最小净宽度不应小于1．5m，A选项错误；高层公共建筑单面布房时，疏散走道的最小净宽度不应小于1．3m，B选项正确；根据3．7．5，厂房内疏散走道的最小净宽度不宜小于1．40m，C选项正确；根据《人民防空工程设计防火规范》GB 50098—2009表5．1．6，人防工程中商场单面布房时的疏散走道净宽度不应小于1．50m，D选项正确；根据5．5．20，剧场观众厅内疏散走道的净宽度应按每100人不小于0．60m计算，且不应小于1．00m，E选项错误。本题答案为BCD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]