[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935630":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935630,605,1,"单选题","对某建筑高度为280 m的综合商业楼进行检查，其避难层（间）设置不符合规范规定的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","避难层设置消防电梯出口",false,{"key":16,"text":17,"correct":14},"B","从首层到第一个避难层之间的高度为48 m，相邻避难层之间的高度为49 m",{"key":19,"text":20,"correct":21},"C","避难间位置靠近楼梯间并采用耐火极限不低于2．00 h的防火隔墙和乙级防火门与其他部位分隔",true,{"key":23,"text":24,"correct":14},"D","避难间的净面积能满足设计避难人员避难的要求，每个护理单元面积为30 m2","考虑到目前国内主战举高消防车——50m高云梯车的操作要求，从首层到第一个避难层之间的高度不大于50 m，两个避难层之间的高度以不大于50 m为宜，故选项B正确。避难层设置消防电梯出口，故选项A正确。避难间位置靠近楼梯间并采用耐火极限不低于2.00 h的防火隔墙和甲级防火门与其他部位分隔，故选项C错误。避难间的净面积能满足设计避难人员避难的要求，并按每个护理单元不小于25.0 m2确定，当避难间兼作其他用途时，需保证其避难安全和可供避难的净面积不变，故选项D正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]