[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935625":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935625,605,1,"单选题","某三级耐火等级的2层丙类厂房，每层划分为一个防火分区。下列关于该厂房的做法，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","厂房内最远点到最近安全出口之间的直线距离为37m",false,{"key":16,"text":17,"correct":18},"B","二层设置两个安全出口，其中2个相邻的安全出口之间的距离最小为4m",true,{"key":20,"text":21,"correct":14},"C","厂房内疏散走道的最小净宽度为1．4m",{"key":23,"text":24,"correct":14},"D","厂房内设置封闭楼梯间","根据《建筑设计防火规范》GB 50016—2014（2018年版）3．2．2，高层厂房的耐火等级不应低于二级，该厂房耐火等级为三级，可判断为多层厂房。根据表3．7．4，丙类三级耐火等级多层厂房内任一点至最近安全出12的直线距离不应大于40m，A选项正确；根据3．7．1，厂房的安全出口应分散布置，每个防火分区或一个防火分区的每个楼层，其相邻2个安全出口最近边缘之间的水平距离不应小于5m，B选项错误；根据3．7．5，厂房内疏散走道的最小净宽度不宜小于1．40m，C选项正确；根据3．7．6，高层厂房和甲、乙、丙类多层厂房的疏散楼梯应采用封闭楼梯间或室外楼梯，D选项正确。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]