[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935621":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935621,605,2,"多选题","某人防工程内设有商场、歌舞厅、电影院以及各类设备用房，下列关于部位之间防火分隔措施的做法中，错误的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","电影院的观众厅与舞台之间的隔墙，耐火极限为2.50h",false,{"key":16,"text":17,"correct":14},"B","消防控制室与其他部位之间的隔墙，耐火极限为2.00h，墙上设置常闭的甲级防火门",{"key":19,"text":20,"correct":21},"C","通信机房与其他部位之间的隔墙，耐火极限为2.00h，墙上设置常闭的乙级防火门",true,{"key":23,"text":24,"correct":21},"D","柴油发电机房的储油间，墙上设置常闭的甲级防火门，并设置高100mm的不燃烧、不渗漏的门槛",{"key":26,"text":27,"correct":21},"E","电影院放映室采用耐火极限为0.50的隔墙与其他部位分隔","CDE","《人民防空工程防火设计规范》（GB 50098-2009），4.2.3和4.2.4，选项C，应为甲级防火门。选项D，门槛高度应为150mm。选项E，耐火极限不应低于1.00h。 电影院、礼堂的观众厅与舞台之间的墙耐火极限不应低于2.50h ，电影院放映室（卷片室）应采用耐火极限不低于1.00h 的隔墙与其他部位隔开，观察窗和放映孔应设置阻火闸门。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]