[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935620":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935620,605,2,"多选题","近年来，很多餐饮、商店等商业设施都通过有顶棚的步行街连接，与步行街相连的商业设施内一旦发生火灾，如果控制不好，很容易造成火灾的蔓延。下列关于某步行街的设置，不符合规范要求的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","步行街两侧建筑的耐火等级不应低于二级",false,{"key":16,"text":17,"correct":18},"B","步行街两侧建筑的商铺之间设置耐火极限1.50h的防火隔墙，每间商铺的建筑面积200 m2",true,{"key":20,"text":21,"correct":18},"C","步行街内任一点到达最近室外安全地点的直线距离为70m",{"key":23,"text":24,"correct":14},"D","步行街两侧建筑的商铺面向步行街一侧围护构件的耐火极限为1．50h，采用乙级防火门",{"key":26,"text":27,"correct":14},"E","相邻商铺之间面向步行街一侧设置宽度为1．5m、耐火极限1．00h的实体墙","BC","B错，步行街两侧建筑的商铺之间应设置耐火极限不低于2．00h的防火隔墙，每间商铺的建筑面积不宜大于300 m2；C错，步行街内任一点到达最近室外安全地点的步行距离不应大于60m；D正确，步行街两侧建筑的商铺面向步行街一侧围护构件的耐火极限不应低于1．00h，并采用乙级防火门；E正确，相邻商铺之间面向步行街一侧应设置宽度不小于1．0m、耐火极限不低于1．00h的实体墙。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]