[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935619":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935619,605,2,"多选题","建筑内的管道和管道井是火灾烟气和火灾蔓延的通道之一，在对竖向井道进行检查时，符合规范要求的包括（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","电缆井在每层楼板处采用难燃材料封堵",false,{"key":16,"text":17,"correct":18},"B","电缆井道井壁耐火极限不低于1．00 h，井壁上的检查门为丙级防火门",true,{"key":20,"text":21,"correct":18},"C","电梯井独立设置，井内严禁敷设可燃气体和甲、乙、丙类液体管道",{"key":23,"text":24,"correct":18},"D","垃圾斗采用不燃烧材料制作，并能自行关闭",{"key":26,"text":27,"correct":18},"E","电梯门的耐火极限不低于1．00 h，并同时符合相关完整性和隔热性要求","BCDE","建筑内竖向井道设置要求：（1）建筑的电缆井、管道井、排（气）烟道、垃圾道等竖向井道，均应分别独立设置。井壁耐火极限不低于1．00 h，井壁上的检查门采用丙级防火门。（2）建筑内的垃圾道排气口应直接开向室外，该前室的门采用丙级防火门。垃圾斗采用不燃材料制作，并能自行关闭。（3）电梯井独立设置。井内严禁敷设可燃气体和甲、乙、丙类液体管道，且不得敷设与电梯无关的电缆、电线等。井壁除开设电梯门、安全逃生门和通气孔洞外，不得开设其他开口。电梯门的耐火极限不应低于1．00 h，并同时符合相关完整性和隔热性要求。（4）建筑内电缆井、管道井与房间、走道等相连通的孔隙，采用防火封堵材料封堵。建筑内电缆井、管道井在每层楼板处采用不低于楼板耐火极限的不燃材料或防火封堵材料封堵。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]