[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935617":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935617,605,2,"多选题","某带顶棚的步行街，且步行街两侧的建筑需利用步行街进行安全疏散时，下列关于步行街两侧商铺的防火分隔措施的说法中，错误的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","商铺之间应采用防火墙进行防火分隔",true,{"key":16,"text":17,"correct":18},"B","每间商铺的建筑面积不宜大于300㎡",false,{"key":20,"text":21,"correct":14},"C","商铺面向步行街一侧的围护结构的耐火极限不应低于1．50h",{"key":23,"text":24,"correct":18},"D","商铺面向步行街一侧的围护结构可采用实体墙、防火玻璃墙",{"key":26,"text":27,"correct":18},"E","相邻商铺之间面向步行街一侧的实体墙，耐火极限不应低于1．00h","AC","根据《建筑设计防火规范》GB 50016—2014（2018年版）5．3．6—3，步行街两侧建筑的商铺之间应设置耐火极限不低于2．00h的防火隔墙，每间商铺的建筑面积不宜大于300㎡，A选项错误，B选项正确；根据5．3．6—4，步行街两侧建筑的商铺，其面向步行街一侧的围护构件的耐火极限不应低于1．00h，并宜采用实体墙，其门、窗应采用乙级防火门、窗：当采用防火玻璃墙（包括门、窗）时，其耐火隔热性和耐火完整性不应低于1．00h；当采用耐火完整性不低于1．00h的非隔热性防火玻璃墙（包括门、窗）时，应设置闭式自动喷水灭火系统进行保护。相邻商铺之间面向步行街一侧应设置宽度不小于1．0m、耐火极限不低于1．00h的实体墙，C选项错误，DE选项正确。本题答案为AC。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]