[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935591":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935591,605,1,"单选题","一厂房，室内净空高度8m，且具有自然对流条件，下列该厂房防烟分区的长边设置不符合要求的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","50m",false,{"key":16,"text":17,"correct":14},"B","60m",{"key":19,"text":20,"correct":14},"C","40m",{"key":22,"text":23,"correct":24},"D","80m",true,"防烟分区的长边一般不大于60m，当室内高度超过6m且具有自然对流条件时，长边不应大于75m。 建筑防烟排烟系统技术标准 GB51251-2017—— 4.2.4 公共建筑、工业建筑防烟分区的最大允许面积及其长边最大允许长度应符合表4.2.4的规定，当工业建筑采用自然排烟系统时，其防烟分区的长边长度尚不应大于建筑内空间净高的8倍。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]