[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935580":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935580,605,1,"单选题","对挡烟垂壁进行检查时，需要注意搭接宽度，下列情况中不符合相关要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","卷帘式挡烟垂壁挡烟部件由两块或两块以上织物缝制，搭接宽度为30 mm",false,{"key":16,"text":17,"correct":18},"B","采用多节垂壁搭接的形式使用，卷帘式挡烟垂壁的搭接宽度为80 mm",true,{"key":20,"text":21,"correct":14},"C","翻板式挡烟垂壁的搭接宽度为20 mm",{"key":23,"text":24,"correct":14},"D","宽度测量值的允许负偏差为规定值的4％","卷帘式挡烟垂壁挡烟部件由两块或两块以上织物缝制时，搭接宽度不得小于20 mm；当单节挡烟垂壁的宽度不能满足防烟分区要求，采用多节垂壁搭接的形式使用时，卷帘式挡烟垂壁的搭接宽度不得小于100 mm；翻板式挡烟垂壁的搭接宽度不得小于20 mm。宽度测量值的允许负偏差不得大于规定值的5％。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]