[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935579":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935579,605,1,"单选题","建筑幕墙是由金属构件和玻璃板等组成的建筑物外围护结构，建筑幕墙外立面开口之间的防火设置不符合规范要求的做法是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","无自动喷水灭火系统下，设置耐火极限为1．0 h的不燃性实体墙，不燃性实体墙高度为1．0 m",true,{"key":16,"text":17,"correct":18},"B","无自动喷水灭火系统下，设置耐火完整性为1．0 h的防火玻璃墙，防火玻璃墙高度为1．2 m",false,{"key":20,"text":21,"correct":18},"C","室内设置自动喷水灭火系统，防火玻璃墙高度为0．8m",{"key":23,"text":24,"correct":18},"D","室内设置自动喷水灭火系统，不燃性实体墙高度为0．8 m","外立面开口之间的防火措施：建筑外墙上在上、下层开口之间，如果采用实体墙分隔，当室内设置自动喷水灭火系统时，墙体的高度不应小于0．8 m，否则墙体的高度不应小于1．2 m；如果采用防火挑檐分隔，挑檐的宽度不应小于1．0 m、长度不小于开口宽度；如果上、下层开口之间因实体墙设置有困难，采用防火玻璃墙分隔，对于高层建筑，防火玻璃墙的耐火完整性不低于1．00 h，对于多层建筑，防火玻璃墙的耐火完整性不低于0．50 h。对于住宅建筑，还需要检查外墙上相邻户开口之间的墙体宽度，如果小于1．0 m，开口之间要设置凸出外墙不小于0．6 m的隔板。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]