[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935578":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935578,605,1,"单选题","根据《建筑内部装修设计防火规范》（GB 50222），对不同建筑防烟楼梯间前室进行检查时，不符合规范要求的做法是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","高层办公楼防烟楼梯间使用面积为6 m2",false,{"key":16,"text":17,"correct":18},"B","商场大楼防烟楼梯间建筑面积为6 m2",true,{"key":20,"text":21,"correct":14},"C","五层住宅楼防烟楼梯间使用面积为5 m2",{"key":23,"text":24,"correct":14},"D","高层厂房合用防烟楼梯间使用面积为11 m2","防烟楼梯间前室的使用面积为：公共建筑、高层厂房（仓库）不应小于6．0 m2，住宅建筑不应小于4．5 m2；所设前室可与消防电梯间前室合用，合用前室的使用面积为：公共建筑、高层厂房（仓库）不应小于10．0m2，住宅建筑不应小于6．0 m2。选项B中为建筑面积，使用面积小于6．0 m2，故选项B错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]