[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935569":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935569,605,2,"多选题","下列工业建筑中，划分防火分区的防火墙不可以采用防火卷帘或防火水幕替代的有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","三级耐火等级的沥青、石蜡仓库",true,{"key":16,"text":17,"correct":14},"B","二级耐火等级的次氯酸钙生产厂房",{"key":19,"text":20,"correct":14},"C","二级耐火等级的硝酸铵仓库",{"key":22,"text":23,"correct":24},"D","二级耐火等级的松香提炼厂房",false,{"key":26,"text":27,"correct":14},"E","二级耐火等级的赛璐珞厂房","ABCE","根据《建筑设计防火规范》GB 50016—2014（2018年版）3．3．2—1，仓库内的防火分区之间必须采用防火墙分隔，甲、乙类仓库内防火分区之间的防火墙不应开设门、窗、洞口；AC选项正确； 根据3．3．1注1，防火分区之间应采用防火墙分隔，除甲类厂房外的一、二级耐火等级厂房，当其防火分区的建筑面积大于本表规定，且设置防火墙确有困难时，可采用防火卷帘或防火分隔水幕分隔，BE选项正确，D选项错误。本题答案为ABCE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]