[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935557":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935557,605,1,"单选题","某地上6层办公大楼，层高4m，每层划分为两个防火分区，当每个防火分区的通风、空气调节系统均独立设置时，该系统风管穿过建筑的哪个部位可不设置防火阀（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","穿越防火分区处",false,{"key":16,"text":17,"correct":14},"B","穿越防火分隔处的变形缝两侧",{"key":19,"text":20,"correct":21},"C","水平风管与竖向总管的交接处",true,{"key":23,"text":24,"correct":14},"D","穿越通风、空气调节机房的房间隔墙处","根据《建筑设计防火规范》GB 50016—2014（2018年版）9．3．11，通风、空气调节系统的风管在下列部位应设置公称动作温度为70℃的防火阀：1）穿越防火分区处；2）穿越通风、空气调节机房的房间隔墙和楼板处：3）穿越重要或火灾危险性大的场所的房间隔墙和楼板处；4）穿越防火分隔处的变形缝两侧；5）竖向风管与每层水平风管交接处的水平管段上。注：当建筑内每个防火分区的通风、空气调节系统均独立设置时，水平风管与竖向总管的交接处可不设置防火阀。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]