[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935545":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935545,605,1,"单选题","某2层自行车装配厂房，耐火等级为二级，层高5m，二层设置有一个单层润滑油中间仓库，库房内未设置自动喷水灭火系统，则该中间仓库每个防火分区的最大允许面积为（ ）㎡。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1000",false,{"key":16,"text":17,"correct":18},"B","700",true,{"key":20,"text":21,"correct":14},"C","2000",{"key":23,"text":24,"correct":14},"D","1200","根据《建筑防火设计规范》GB 50016—2014（2018年版）3．3．6条文说明，在厂房内设置中间仓库时，生产车间和中间仓库的耐火等级应当一致，且该耐火等级要按仓库和厂房两者中要求较高者确定。同时由于该中间仓库设置在多层厂房内，所以也应该按多层仓库来确定中间仓库防火分区的最大允许面积。二级耐火等级丙类1项多层仓库的防火分区的最大允许面积为700㎡。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]