[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935542":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935542,605,1,"单选题","某建筑高度24．2m的医疗建筑，设有两层裙房，裙房与主体用耐火极限为3．00h的防火卷帘完全分隔，则裙房的防火分区最大允许建筑面积可为（ ）㎡。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","2500",false,{"key":16,"text":17,"correct":18},"B","3000",true,{"key":20,"text":21,"correct":14},"C","5000",{"key":23,"text":24,"correct":14},"D","1500","根据《建筑设计防火规范》GB 50016—2014（2018年版）表5．1．1，该医疗建筑为一类高层民用建筑，裙房与主体之间采用防火卷帘，而非防火墙分隔，防火分区不能按单、多层划分，应按主体确定，一、二级高层民用建筑防火分区最大面积为1500㎡，一类高层应设自动喷水灭火系统，防火分区面积增加一倍，裙房的消防设施也随主体，故该裙房的防火分区面积最大可为3000㎡。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]