[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935537":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935537,605,2,"多选题","某汽车轮毂打磨厂房，地上2层，建筑高度为12 m，建筑面积为5600 m2。在防火检查时获取的下列信息中，正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","屋顶钢承重构件涂刷防火涂料保护，耐火极限达到1．0 h",true,{"key":16,"text":17,"correct":14},"B","除尘管道避开厂房的梁、柱，沿外墙布置",{"key":19,"text":20,"correct":21},"C","一层设置办公室，并采用防火墙和耐火极限不低于1．5 h的楼板与其他部位分隔",false,{"key":23,"text":24,"correct":14},"D","厂房设封闭楼梯间，并采用乙级防火门",{"key":26,"text":27,"correct":14},"E","排风除尘设备集中布置在室外独立的建筑内，该建筑外墙与厂房的防火间距为10 m","ABDE","首先判断该厂房为乙类有粉尘爆炸危险的厂房，乙类厂房的耐火等级至少为二级，二级屋顶承重构件要求不燃、耐火极限不低于1．00 h，故选项A正确。《建筑设计防火规范》（GB 50016）规定，有爆炸危险的甲、乙类生产部位，宜布置在单层厂房靠外墙的泄压设施或多层厂房顶层靠外墙的泄压设施附近。有爆炸危险的设备宜避开厂房的梁、柱等主要承重构件布置，故选项B正确。甲、乙类厂房内严禁设置办公室，故选项C错误。净化有爆炸危险粉尘的干式除尘器和过滤器宜布置在厂房外的独立建筑内，且建筑外墙与所属厂房的防火间距不应小于10 m。对符合一定条件可以布置在厂房内的单独房间时，须检查是否采用耐火极限不低于3．00 h的防火隔墙和耐火极限不低于1．50 h的楼板与其他部位分隔。故选项E正确。高层厂房和甲 乙 丙类多层厂房的疏散楼梯应采用封闭楼梯间或室外楼梯，封闭楼梯间采用乙级防火门。故选项D正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]