[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935527":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935527,605,2,"多选题","关于附设在民用建筑内燃油、燃气锅炉房的平面布置，下列说法不正确的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","不应设置在人员密集场所的上一层、下一层或贴邻",false,{"key":16,"text":17,"correct":14},"B","应设置在首层或地下一层靠外墙部位",{"key":19,"text":20,"correct":21},"C","设在屋顶的常（负）压燃油锅炉与屋顶安全出口的距离应不大于6m",true,{"key":23,"text":24,"correct":14},"D","采用相对密度≥0．75的可燃气体的常（负）压燃气锅炉不得设置在地下、半地下",{"key":26,"text":27,"correct":21},"E","布置在首层时，疏散门应直通室外或疏散走道","CE","根据《建筑设计防火规范》GB 50016—2014（2018年版）5．4．12—1，燃油或燃气锅炉房、变压器室应设置在首层或地下一层的靠外墙部位，但常（负）压燃油或燃气锅炉可设置在地下二层或屋顶上，设置在屋顶上的常（负）压燃气锅炉，距离通向屋面的安全出口不应小于6m；采用相对密度（与空气密度的比值）不小于0．75的可燃气体为燃料的锅炉，不得设置在地下或半地下：根据5．4．12—2锅炉房、变压器室的疏散门均应直通室外或安全出口。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]