[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935525":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935525,605,2,"多选题","某单层厂房用于生产乙醇（总建筑面积6000㎡），下列关于其防火设计的描述中，正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","该厂房内采用耐火极限为3．00h的防火墙划分防火分区",false,{"key":16,"text":17,"correct":18},"B","与该厂房贴邻布置的办公室采用二级耐火等级且设有独立安全出口，两者之间采用耐火极限为3．00h的防爆墙分隔",true,{"key":20,"text":21,"correct":14},"C","为满足24小时值班需求，在该厂房内靠外墙侧设置一间有独立安全出口且仅住宿两人的宿舍",{"key":23,"text":24,"correct":14},"D","该厂房的10KV的专用变配电室设在厂房内靠外墙一角",{"key":26,"text":27,"correct":18},"E","该厂房外贴临设置一间一级耐火等级有独立安全出口的值班室，值班室与该厂房采用3．00h的防爆墙分隔","BE","该乙醇厂房为甲类厂房，根据《建筑设计防火规范》GB 50016—2014（2018年版）3．2．9，甲、乙类厂房和甲、乙、丙类仓库内的防火墙，其耐火极限不应低于4．00h，A选项错误；根据3．3．5，员工宿舍严禁设置在厂房内，办公室、休息室等不应设置在甲、乙类厂房内，确需贴邻本厂房时，其耐火等级不应低于二级，并应采用耐火极限不低于3．00h的防爆墙与厂房分隔，且应设置独立的安全出口，BE选项正确，C选项错误，根据3．3．8，变、配电站不应设置在甲、乙类厂房内或贴邻，且不应设置在爆炸性气体、粉尘环境的危险区域内，供甲、乙类厂房专用的10KV及以下的变、配电站，当采用无门、窗、洞口的防火墙分隔时，可一面贴邻，并应符合现行国家标准《爆炸危险环境电力装置设计规范》GB 50058等标准的规定，D选项错误。本题答案为BE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]