[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935520":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935520,605,1,"单选题","某铝合金冷加工厂房，地上2层，建筑高度12m。下列关于该厂房的平面布置，存在火灾隐患的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","在一层设置一间工人休息室，采用耐火极限为2．00h的防火隔墙与其他部位分隔",false,{"key":16,"text":17,"correct":14},"B","在二层中间设置一间铝合金条中间仓库，采用耐火极限2．00h的防火隔墙和1．50h的楼板与生产部位分隔",{"key":19,"text":20,"correct":21},"C","在二层设置一个容量为3m2的润滑油储罐，采用耐火极限2．50h的防火隔墙和甲级防火门与生产部位分隔",true,{"key":23,"text":24,"correct":14},"D","设置在厂房内的通风机房，采用耐火极限1．00h的防火隔墙和0．50h的楼板与其他部位分隔","设置中间储罐的房间，采用耐火极限不低于3．00h的防火隔墙和耐火极限不低于1．50h的楼板与其他部位分隔，房间门采用甲级防火门。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]