[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935484":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935484,605,2,"多选题","某综合楼，共40层，每层4m，消防技术服务机构对该建筑进行防火检查时，存在下列情况。其中符合规范要求的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","移动营业厅设置在地下三层",false,{"key":16,"text":17,"correct":18},"B","消防控制室设置在建筑的地下一层",true,{"key":20,"text":21,"correct":14},"C","消防控制室采用耐火极限不低于2．00h的防火隔墙和耐火极限不低于1．50h的楼板与其他部位分隔",{"key":23,"text":24,"correct":18},"D","消防水泵房设置在地下二层",{"key":26,"text":27,"correct":14},"E","建筑内的防烟、排烟风机设置在一个房间内","BD","A错，营业厅、展览厅不得设置在地下三层及以下楼层。C选项错误，本题中建筑是超高层，1.5h的楼板是不满足要求的。E错，设置在建筑内的防排烟风机应设置在不同的专用机房内。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]