[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935471":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935471,605,1,"单选题","下列划分防火分区的分隔措施做法中，不符合相关规定的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","某多层商业广场，防火分区之间直接采用加气混凝土砌块的防火墙，耐火极限为4．00h",false,{"key":16,"text":17,"correct":18},"B","某三级耐火等级的针织品厂房，防火分区之间采用3．00h的防火卷帘分隔",true,{"key":20,"text":21,"correct":14},"C","某漂白粉存储仓库，防火分区之间采用无任何门窗洞口的防火墙分隔",{"key":23,"text":24,"correct":14},"D","某单层冰醋裂解厂房，防火分区之间采用防火墙分隔，防火墙上设火灾时能自动关闭的甲级防火门","服装加工厂、漂白粉仓库、冰醋裂解厂房的火灾危险性分别为丙类、乙类、甲类：根据《建筑设计防火规范》GB 50016—2014（2018年版）表3．3．1注1，防火分区之间应采用防火墙分隔。除甲类厂房外的一、二级耐火等级厂房，当其防火分区的建筑面积大于本表规定，且设置防火墙确有困难时，可采用防火卷帘或防火分隔水幕分隔，B选项错误； 根据3．3．2注1，仓库内的防火分区之间必须采用防火墙分隔，甲、乙类仓库内防火分区之间的防火墙不应开设门、窗、洞口，C选项正确； 根据6．1．5，防火墙上不应开设门、窗、洞口，确需开设时，应设置不可开启或火灾时能自动关闭的甲级防火门、窗，D选项正确。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]