[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935466":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935466,605,2,"多选题","下列关于设置在民用建筑内的燃油锅炉房、柴油发电机房的说法中，不正确的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","燃料供给管道在进入建筑物之前或设备间内的管道上应设置自动关断阀",true,{"key":16,"text":17,"correct":14},"B","储油间与锅炉间之间应采用不低于3．00h的防火墙进行分隔",{"key":19,"text":20,"correct":14},"C","应设置能储存全部油量的事故储油设施",{"key":22,"text":23,"correct":24},"D","储油箱应密闭，并设置通向室外的通气管，通气管上设置带阻火器的呼吸阀",false,{"key":26,"text":27,"correct":14},"E","油箱的储油量不宜超过1昼夜的需要量","ABCE","根据《建筑设计防火规范》GB 50016—2014（2018年版）5．4．15，设置在建筑内的锅炉、柴油发电机，其燃料供给管道应符合下列规定：在进入建筑物前和设备间内的管道上均应设置自动和手动切断阀；储油间的油箱应密闭且应设置通向室外的通气管，通气管应设置带阻火器的呼吸阀，油箱的下部应设置防止油品流散的设施．AC选项错误，D选项正确；根据5．4．12—4，锅炉房内设置储油间时，其总储存量不应大于1m3，且储油间应采用耐火极限不低于3．00h的防火隔墙与锅炉间分隔，B选项错误：根据5．4．13—4，机房内设置储油间时，其总储存量不应大于1m3，储油间应采用耐火极限不低于3．00h的防火隔墙与发电机间分隔，E选项错误。本题答案为ABCE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]