[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935464":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935464,605,1,"单选题","下列关于医院和疗养院平面布置的说法中，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","医院和疗养院的住院部分设置在地下一层时，与室外地坪高差不应大于10m",true,{"key":16,"text":17,"correct":18},"B","医院和疗养院的住院部分采用三级耐火等级建筑时，不应超过2层",false,{"key":20,"text":21,"correct":18},"C","医院和疗养院的病房楼内相邻护理单元之间隔墙上的门应采用乙级防火门",{"key":23,"text":24,"correct":18},"D","医院和疗养院的病房楼内相邻护理单元之间隔墙上的耐火极限不应低于2.00h","《建筑设计防火规范》（GB 50016-2014），5.4.5，医院和疗养院的住院部分不应设置在地下或半地下。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]