[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935460":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935460,605,1,"单选题","对民用建筑内柴油发电机房进行检查时，不正确的设置是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","布置在建筑物的地下二层",false,{"key":16,"text":17,"correct":14},"B","机房内设置储油间的总储存量为1m3",{"key":19,"text":20,"correct":14},"C","储油间采用耐火极限为3．00 h的防火隔墙与发电机间分隔",{"key":22,"text":23,"correct":24},"D","储油间防火隔墙上设置乙级防火门",true,"柴油发电机房设置要求：（1）设置层数。柴油发电机房不应布置在人员密集场所的上一层、下一层或贴邻，宜布置在建筑物的首层及地下一、二层。（2）与建筑其他部位的防火分隔。采用耐火极限不低于2．00 h的防火隔墙和耐火极限不低于1．50 h的不燃性楼板与其他部位分隔，门采用甲级防火门。（3）储油间的设置。机房内设置储油间的总储存量不应大于1 m3，且储油间采用耐火极限不低于3．00 h的防火隔墙与发电机间分隔；确需在防火隔墙上开门时，设置甲级防火门。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]