[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935437":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935437,605,2,"多选题","对下列建筑的防火分隔措施进行检查，不符合现行国家消防技术标准的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","橡胶厂的压缩车间防火分区之间采用耐火极限为3．00h的防火墙",false,{"key":16,"text":17,"correct":14},"B","医疗建筑内的贵重精密医疗装备用房采用耐火极限为2．00h的防火隔墙和1．50h的楼板与其他场所或部位分隔",{"key":19,"text":20,"correct":21},"C","中药材成品仓库内的休息室采用耐火极限为2．00h的防火隔墙和1．50h的楼板与其他部位分隔",true,{"key":23,"text":24,"correct":21},"D","木器加工厂内的丙类液体中间储罐间采用耐火极限为2．50h的防火隔墙和1．50h的楼板与其他部位分隔",{"key":26,"text":27,"correct":21},"E","铝粉存储仓库内的办公室采用耐火极限为3．00h的防火墙和1．50h的楼板与其他部位分隔","CDE","根据《建筑设计防火规范》GB 50016—2014（2018年版）表3．1．1，橡胶厂的压缩车间、木器厂的火灾危险级别均为丙类，根据表3．1．2，中药材成品库、铝粉仓库的火灾危险级别分别为丙类、乙类，根据表3．3．1注1，防火分区之间应采用防火墙分隔，A选项正确；根据6．2．2，医疗建筑内的贵重精密医疗装备用房，应采用耐火极限不低于2．00h的防火隔墙和1．00h的楼板与其他场所或部位分隔，墙上必须设置的门、窗应采用乙级防火门、窗，B选项正确；根据3．3．9，办公室、休息室等严禁设置在甲、乙类仓库内，也不应贴邻，办公室、休息室设置在丙、丁类仓库内时，应采用耐火极限不低于2．50h的防火隔墙和1．00h的楼板与其他部位分隔，并应设置独立的安全出口。隔墙上需开设相互连通的门时，应采用乙级防火门，CE选项错误；根据3．3．7，厂房内的丙类液体中间储罐应设置在单独房间内，其容量不应大于5m3。设置中间储罐的房间，应采用耐火极限不低于3．00h的防火隔墙和1．50h的楼板与其他部位分隔，房闸门应采用甲级防火门，D选项错误。本题答案为CDE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]