[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935430":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935430,605,2,"多选题","某办公楼，设置1部消防电梯、1部客梯。消防机构对该建筑电梯进行检查，下列结果，符合规定的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","消防电梯在首层经过30m长的走道通向室外",true,{"key":16,"text":17,"correct":14},"B","在首层的消防电梯入口处设置供消防队员专用的操作按钮",{"key":19,"text":20,"correct":21},"C","消防电梯轿厢的内部装修采用铝塑板纤维石膏板",false,{"key":23,"text":24,"correct":21},"D","普通客梯井道内设置煤气管道",{"key":26,"text":27,"correct":21},"E","消防电梯井道设置排烟风机电缆","AB","根据《建筑设计防火规范》GB 50016—2014（2018年版）7．3．5，除设置在仓库连廊、冷库穿堂或谷物筒仓工作塔内的消防电梯外，消防电梯应设置前室，并应符合下列规定：前室宜靠外墙设置，并应在首层直通室外或经过长度不大于30m的通道通向室外；A选项正确；根据7．3．8，消防电梯在首层的消防电梯入口处应设置供消防队员专用的操作按钮，B选项正确；根据7．3．8，消防电梯轿厢的内部装修应采用不燃材料；而铝塑板属难燃材料，C选项错误；根据6．2．9，电梯井应独立设置，井内严禁敷设可燃气体和甲、乙、丙类液体管道，不应敷设与电梯无关的电缆、电线等；电梯井的井壁除设置电梯门、安全逃生门和通气孔洞外，不应设置其他开口，DE选项错误。本题答案为AB。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]