[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935378":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935378,605,2,"多选题","对某电解食盐厂进行防火检查，检查结果如下，其中不符合规范要求的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","该厂房的承重结构采用砖混结构",true,{"key":16,"text":17,"correct":18},"B","该厂房的总控制室独立设置",false,{"key":20,"text":21,"correct":14},"C","厂房内与楼梯间连通部位设置有门斗，门采用乙级防火门与楼梯间的门错位",{"key":23,"text":24,"correct":14},"D","采用热风循环供暖，循环使用前经净化处理，使空气中的含尘浓度低于其爆炸下限的25％",{"key":26,"text":27,"correct":14},"E","防火分区之间，采用耐火极限为4．00h的防火卷帘","ACDE","电解食盐厂房火灾危险性属于甲类，根据《建筑设计防火规范》GB 50016-2014（2018年版）3．6．1，有爆炸危险的甲、乙类厂房宜独立设置，并宜采用敞开或半敞开式。其承重结构宜采用钢筋混凝土或钢框架、排架结构，A选项错误；根据3．6．8，有爆炸危险的甲、乙类厂房的总控制室应独立设置，B选项正确；根据3．6．10，有爆炸危险区域内的楼梯间、室外楼梯或有爆炸危险的区域与相邻区域连通处，应设置门斗等防护措施。门斗的隔墙应为耐火极限不应低于2．00h的防火隔墙，门应采用甲级防火门并应与楼梯间的门错位设置，C选项错误；根据9．1．2，甲、乙类厂房内的空气不应循环使用，D选项错误；根据3．3．1注1，甲类厂房防火分区之间应采用防火墙分隔，E选项错误。本题答案为ACDE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]